A double check valve assembly, or DCVA, has two independent spring-loaded checks between two resilient-seated shutoffs and four test cocks. It is approved for low-hazard connections, so you see it on many fire lines, apartment services and some irrigation systems.

The tester bleeds and reads each check separately. Each one has to hold a differential of at least 1.0 psid. If a check reads lower, the cause is usually a worn rubber disc, a weak spring or debris across the seat.

Unlike an RPZ, a DCVA can be installed in a pit or vault in many jurisdictions, which brings its own problems. Flooded vaults make test cocks hard to reach and corrode the bolts. Testers often pump the vault before they can start.

Grizzly Backflow & Plumbing connects you with local testers in Newark, NY for double check valve testing, report filing with your purveyor and repair if a check fails. Good backflow prevention depends on both checks holding, not one. Call (833) 990-5874.

How it works

Four steps to backflow testing in Newark, NY

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across Newark, NY

Backflow testing for the neighborhoods and ZIP codes around Newark, NY.

Neighborhoods we cover for backflow testing

  • Newark

ZIP codes we serve

14513

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about Double Check Valve Testing in Newark, NY.

Talk to a person
Who is allowed to test my backflow device?
A tester who holds a backflow tester certification recognized by your state or your water utility. Many utilities keep an approved tester list and reject reports signed by anyone not on it.
What happens if I miss the backflow test deadline?
Utilities usually send a second notice, and after that some add a fee or schedule a service shutoff. Calling (833) 990-5874 before the deadline is the simplest way to avoid it.
What is a cross-connection?
Any point where drinking water piping can come into contact with a non-potable source. Common examples are a hose in a bucket, a boiler fill line and an irrigation system.
Is fire sprinkler backflow testing different?
Yes. Along with the standard check valve test, NFPA 25 calls for an annual forward flow test on fire line backflow assemblies. Results often go to both the water utility and the fire authority.
Can a backflow preventer be repaired instead of replaced?
Often it can. Rebuild kits with new discs, springs and seals are sold for most brands. Replacement makes more sense when the body is cracked or parts are no longer made.